Skip to Main Content
AVEVA Product Feedback


Status No status
Created by Guest
Created on Aug 20, 2022

Allow Calculation Wait Time to be set at the analysis rather than server level

The CalculationWaitTimeInSeconds applies to the entire server but different calculations will have differing requirements of promptness and accuracy (and accuracy can be mitigated with the Recalculation option)
  • Attach files
  • Nathan Anderson
    Apr 21, 2026

    Use case: EF generating analytics, so no auto recalculation is available.

    Analytics with multiple triggers must account for the latency for every data stream - otherwise EF's can and will end witn incorrect end times. If for example there are two tags of 60 second scan classes, we must add the two latency's together (in this case 2 minutes) then set the tuning parameter for the entire analytics engine CalculationWaitTimeInSeconds to be greater. This not feasible for built out systems, my system would require a 10 minute setting.


    allowing a CalculationWaitTimeInSeconds setting per analytic or a collection delay timer per analytic would allow PI to properly collect all inputs.

  • Vincent Witzel
    Aug 20, 2022
    My customer has a similar need. For what it's worth, this request appears to be similar to this one: https://feedback.osisoft.com/forums/555148-pi-server/suggestions/37048084-delayed-triggers-for-analytics